Contacts.
General. The major function of the air circuit breaker
depends among other things on correct operation of its contacts.
These circuit breakers normally have at least two distinct
sets of contacts on each pole, main and arcing. Some have an
intermediate pair of contacts that open after the main current-
carrying contacts and before the arcing contacts. When
closed, practically the entire load current passes through the
main contacts. Also, high-overload or short-circuit current
pass through them during opening or closing faulted lines. If
the resistance of these contacts becomes high, they will overheat.
Increased contact resistance can be caused by pitted contact
surfaces, foreign material embedded on contact surfaces,
or weakened contact spring pressure. This resistance will
cause excessive current to be diverted through the arcing contacts,
with consequent overheating and burning. The pressure
should be kept normal, which is usually described in the
manufacturer’s instructions.
Arcing Arching contacts are the last to open; any arcing normally
originates on them. In circuit interruption they carry
current only momentarily, but that current might be equal to
the interrupting rating of the breaker. In closing against a
short circuit, they can momentarily carry considerably more
than the short-circuit interrupting rating. Therefore, there
must be positive contact when they are touching. If not, the
main contacts can be badly burned, interrupting heavy faults.
Failure to interrupt might also result.
On magnetic blow-out air breakers, the arc is
quickly removed from the arcing contacts by a magnetic blowout
field and travels to arcing horns, or runners, in the arc
interrupter. The arcing contacts are expendable and will eventually
burn enough to require replacement.
Rules: The general rules for maintaining contacts on all
types of breakers are as follows:
(1) They should be kept clean, smooth, and in good alignment.
(2) The pressure should be kept normal, as prescribed in the
manufacturers’ literature.
Cleaning The main contact surfaces should be clean and
bright. Discoloration of the silvered surfaces, however, is not
usually harmful unless caused by insulating deposits. Insulating
deposits should be removed with alcohol or a silver
cleaner. Slight impressions on the stationary contacts will be
caused by the pressure and wiping action of the movable contacts.
Minor burrs or pitting can be allowed, and projecting
burrs can be removed by dressing. Nothing more abrasive
than crocus cloth should be used on the silvered contact surfaces.
Where serious overheating is indicated by the discoloration
of metal and surrounding insulation, the contacts and
spring assemblies should be replaced in line with the manufacturers’
instructions.
Contact Pressure The circuit breaker should be closed manually to
check for proper wipe, pressure, and contact alignment,
and to ensure that all contacts make at approximately the
same time. The spacing between stationary and movable
contacts should be checked in the fully open position. Adjustments
should be made in accordance with the manufacturers’
recommendations.
Old contacts: Laminated copper or brush-style contacts found on
older circuit breakers should be replaced when badly burned.
Repairs are impractical because the laminations tend to weld
together when burning occurs, and contact pressure and wipe
are greatly reduced. They can be dressed with a file to remove
burrs or to restore their original shape. They should be replaced
when they are burned sufficiently to prevent adequate
circuit-breaker operation or when half of the contact surface is
burned away. Carbon contacts, used on older circuit breakers,
require very little maintenance. However, inadequate contact
pressure caused by erosion or repeated dressing might cause
overheating or interfere with their function as arcing contacts.
The drawout contacts on the circuit breaker and the
stationary contacts in the cubicle should be cleaned and inspected
for overheating, proper alignment, and broken or weak
springs. The contact surfaces should be lightly coated with a contact
lubricant to facilitate ease of the mating operation.
Arc Interrupters.
General. Modern arc interrupters of medium voltage
magnetic blow-out air circuit breakers are built with only inorganic
materials exposed to the arc. Such materials line the
throats of the interrupter and constitute the interrupter plates
or fins, which act to cool and disperse the arc. The insulation
parts of the interrupter remain in the circuit across contacts at
all times. During the time that the contacts are open, these
insulating parts are subject to full potential across the breaker.
The ability to withstand this potential depends on the care
given the insulation.
Particular care should be taken at all times to keep the
interrupter assembly dry. The materials are not affected much
by humidity, but the ceramic material especially will absorb
water.
The interrupters should be inspected each time the
contacts are inspected. Any residue, dirt, or arc products
should be removed with a cloth or by a light sanding. A wire
brush or emery cloth should not be used for this purpose because
of the possibility of embedding conducting particles in
the ceramic material.
Inspection checks An interrupter should be inspected for the following:
(A) Broken or Cracked Ceramic Parts. Small pieces broken
from the ceramics or small cracks are not important. Large
breaks or expansive cracks, however, can interfere with top
performance of the interrupter. Hence, if more than one or
two broken or badly cracked plates are apparent, renewal of
the ceramic stack is indicated.
(B) Erosion of Ceramics. When an arc strikes a ceramic part
in the interrupter, the surface of the ceramic will be melted
slightly. When solidified again, the surface will have a glazed,
whitish appearance. At low and medium currents, this effect is
very slight. However, large-current arcs repeated many times
can boil away appreciable amounts of the ceramic. When this
happens, the ceramic stack assembly should be replaced.
(C) Dirt in Interrupter. While in service, the arc chute assembly
can become dirty. Dust or loose soot deposited on the inside
surface of the arc chute can be removed by vacuuming or
by wiping with cloths that are free of grease or metallic particles.
Deposits can accumulate on ceramic arc shields from
the arcing process. These deposits, from the metal vapors
boiled out of the contacts and arc horns, can accumulate to a
harmful amount in breakers that receive many operations at
low-or medium-interrupting currents. Particular attention
should be paid to any dirt on the plastic surfaces below the
ceramic arc shield. These surfaces should be wiped clean, if
possible, especially if the dirt contains carbon or metallic deposits.
On breakers that operate thousands of times at low and
medium currents, sufficient tightly adhering dirt can accumulate
on the ceramic arc shields to impair proper interrupting
performance. These arc chutes are of a very hard material,
and a hard nonconducting abrasive is necessary for cleaning.
A flexible, abrasive aluminum oxide disc on an electric drill
can be useful in cleaning arc chutes. The ceramic arc shields
might appear dirty and yet have sufficient dielectric strength.
The following insulation test can be used as a guide in determining
when this complete or major cleaning operation is
required. The arc chutes of medium-voltage circuit breakers
should withstand the 60-Hz-rated maximum voltage for one
minute between the front and rear arc horns. In some applications,
circuit breakers can be exposed to overvoltages, in
which case such circuit breakers should have an appropriate
overpotential test applied across the open contacts. Some
manufacturers also recommend a surface dielectric test of the
ceramic surfaces near the contacts to verify adequate dielectric
strength of these surfaces.
Air-puffer devices used to blow the arc up into the
interrupter should be checked for proper operation. One accepted
method is as follows. With the interrupter mounted on
the breaker in its normal position, a piece of tissue paper is
placed over the discharge area of the interrupter and observed
for movement when the breaker is opened. Any perceptible
movement of the paper indicates that the puffer is functioning
properly.
Low-voltage air circuit-breaker arc chutes are of relatively
simple construction, consisting primarily of a wedge-
shaped vertical stack of splitter plates enclosed in an insulating
jacket. An arc chute is mounted on each pole unit directly above
the main contacts. Arc interruptions produce erosion of the splitter
plates. The lower inside surfaces of the insulating jackets will
also experience some erosion and sooty discoloration.
Observation: The arc chutes should be removed and examined as
part of routine maintenance. If the splitter plates are seriously
eroded, they should be replaced. If the interior surfaces of the
enclosing jackets are discolored or contaminated with arc
products, they should be sanded with sandpaper or replaced.
Occasionally, the whole arc chute might need replacing, depending
on the severity of the duty.
Operating Mechanism.
General. The purpose of the operating mechanism
is to open and close the contacts. This usually is done by
linkages connected, for most power breakers, to a power-
operating device such as a solenoid or closing spring for
closing, and that contains one or more small solenoids or
other types of electromagnets for tripping. Tripping is accomplished
mechanically, independently from the closing
device, so that the breaker contacts will open even though
the closing device still might be in the closed position. This
combination is called a mechanically trip-free mechanism.
After closing, the primary function of the operating mechanism
is to open the breaker when it is desired, which is
whenever the tripping coil is energized at above its rated
minimum operating voltage.
Check points The operating mechanism should be inspected for
loose or broken parts, missing cotter pins or retaining keepers,
missing nuts and bolts, and binding or excessive wear. All
moving parts are subject to wear. Long-wearing and corrosion-
resistant materials are used by manufacturers, and some wear
can be tolerated before improper operation occurs.
Excessive wear usually results in the loss of travel of
the breaker contacts. It can affect operation of latches; they
could stick or slip off and prematurely trip the breaker. Adjustments
for wear are provided in certain parts. In others, replacement
is necessary.
The closing and tripping action should be quick
and positive. Any binding, slow action, delay in operation, or
failure to trip or latch must be corrected prior to returning to
service.
The two essentials to apply in maintenance of the
operating mechanism are KEEP IT SNUG and KEEP IT FRICTION
FREE.
Breaker Auxiliary Devices.
The closing motor or solenoid, shunt trip, auxiliary
switches, and bell alarm switch should be inspected for correct
operation, insulation condition, and tightness of connections.
On-off indicators, spring-charge indicators, mechanical
and electrical interlocks, key interlocks, and padlocking
fixtures should be checked for proper operation,
and should be lubricated where required. In particular, the
positive interlock feature that prevents the insertion and
withdrawal of the circuit breaker should be tested while it is
in the closed position.
The protective relay circuits should be checked by
closing the breaker in the test position and manually closing
the contacts of each protective relay to trip the circuit breaker.
.
Trip devices on low-voltage breakers should be tested periodically
for proper calibration and operation with low-voltage/
high-current test devices. Calibration tests should be made to
verify that the performance of the breaker is within the manufacturer’s
published curves. It is very important that manufacturers’
calibration curves for each specific breaker rating be
used. The fact that current-time curves are plotted as a band of
values rather than a single line curve should be taken into
account
If the breakers are equipped with static-tripping devices,
they should be checked for proper operation and timing in line
with the manufacturer’s recommendations. Some manufacturers
recommend replacement of electromagnetic devices with
static devices in the interest of realizing more precision and a
higher degree of reliability with the latter devices.
Molded case circuit breaker
A molded-case circuit breaker consists of two basic
parts. One part consists of the current-carrying conductors,
contacts, and appropriate operating mechanism necessary to
perform the circuit-switching functions. The second part consists
of the protective element, including the tripping mechanism
associated therewith.
.
Application Considerations. Molded-case circuit breakers
will trip from exposure to continuous currents beyond
their ratings, and many trip from unduly high ambient temperatures,
from poor or improper connections, from damaged
plug-in members, and from other conditions that transfer
undue heat to the breaker mechanism. Some of these
conditions violate application specifications. A molded-case
circuit breaker applied in a panelboard should not be loaded
in excess of 80 percent of its continuous current rating, where
in normal operation the load will continue for three hours or
more.
Phase-Fault Current Conditions. A typical molded-case
circuit breaker is equipped with both time-delay and instantaneous
tripping devices. Time-delay tripping has inverse time
characteristics that provide a shorter tripping time for higher
overloads. Under moderate, short-duration overloads, the circuit
breaker allows sufficient time for applications such as motor
starting. Under severe overloads, the circuit breaker will
trip quickly, providing adequate protection for conductors
and insulation. For high-fault currents, the magnetic tripping
device responds to open the circuit breaker immediately.
Ground-Fault Tripping. It should be recognized that
standard molded-case circuit breakers are not generally
equipped with ground-fault sensing and protection devices
and, therefore, will not normally trip and clear low-level
ground faults that can do immense damage.
Types of Molded-Case Circuit Breakers.
Molded-case circuit breakers can generally be divided
into three major categories depending on the type of trip unit
employed:
(1) Factory sealed, noninterchangeable trip
(2) Interchangeable trip
(3) Solid state
.
Types of Maintenance. Maintenance of molded-case circuit
breakers can generally be divided into two categories: mechanical
and electrical. Mechanical maintenance consists of inspection
involving good housekeeping, maintenance of proper
mechanical mounting and electrical connections, and manual
operation as outlined in the following paragraphs.
Inspection and Cleaning. Molded-case circuit breakers
should be kept clean of external contamination so that internal
heat can be dissipated normally. Further, a clean case will
reduce potential arcing conditions between live conductors,
and between live conductors and ground. The structural
strength of the case is important in withstanding the stresses
imposed during fault-current interruptions. Therefore, an inspection
should be made for cracks in the case, and replacements
should be made if necessary.
Loose Connections. Excessive heat in a circuit breaker
can cause a malfunction in the form of nuisance tripping and
possibly an eventual failure. Loose connections are the most
common cause of excessive heat. Periodic maintenance
checks should involve checking for loose connections or evidence
of overheating. Loose connections should be tightened
as required, using manufacturers’ recommended torque values.
Molded-case circuit breakers having noninterchangeable
trip units are properly adjusted, tightened, and sealed at the
factory. Those having interchangeable trip units installed away
from the factory could overheat if not tightened properly during
installation. All connections should be maintained in accordance
with manufacturers’ recommendations.
Mechanical Mechanism Exercise. Devices with moving
parts require periodic checkups. A molded-case circuit
breaker is no exception. It is not unusual for a molded-case
circuit breaker to be in service for extended periods and never
be called on to perform its overload-or short-circuit-tripping
functions. Manual operation of the circuit breaker will help
keep the contacts clean, but does not exercise the tripping
mechanism. Although manual operations will exercise the
breaker mechanism, none of the mechanical linkages in the
tripping mechanisms will be moved with this exercise. Some
circuit breakers have push-to-trip buttons that should be
manually operated in order to exercise the tripping mechanism
linkages.
Friday, February 13, 2009
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment