Contacts. 
 General. The major function of the air circuit breaker 
depends among other things on correct operation of its contacts. 
These circuit breakers normally have at least two distinct 
sets of contacts on each pole, main and arcing. Some have an 
intermediate pair of contacts that open after the main current-
carrying contacts and before the arcing contacts. When 
closed, practically the entire load current passes through the 
main contacts. Also, high-overload or short-circuit current 
pass through them during opening or closing faulted lines. If 
the resistance of these contacts becomes high, they will overheat. 
Increased contact resistance can be caused by pitted contact 
surfaces, foreign material embedded on contact surfaces, 
or weakened contact spring pressure. This resistance will 
cause excessive current to be diverted through the arcing contacts, 
with consequent overheating and burning. The pressure 
should be kept normal, which is usually described in the 
manufacturer’s instructions. 
 Arcing Arching contacts are the last to open; any arcing normally 
originates on them. In circuit interruption they carry 
current only momentarily, but that current might be equal to 
the interrupting rating of the breaker. In closing against a 
short circuit, they can momentarily carry considerably more 
than the short-circuit interrupting rating. Therefore, there 
must be positive contact when they are touching. If not, the 
main contacts can be badly burned, interrupting heavy faults. 
Failure to interrupt might also result. 
 On magnetic blow-out air breakers, the arc is 
quickly removed from the arcing contacts by a magnetic blowout 
field and travels to arcing horns, or runners, in the arc 
interrupter. The arcing contacts are expendable and will eventually 
burn enough to require replacement. 
Rules: The general rules for maintaining contacts on all 
types of breakers are as follows: 
(1) They should be kept clean, smooth, and in good alignment. 
(2) The pressure should be kept normal, as prescribed in the 
manufacturers’ literature. 
Cleaning The main contact surfaces should be clean and 
bright. Discoloration of the silvered surfaces, however, is not 
usually harmful unless caused by insulating deposits. Insulating 
deposits should be removed with alcohol or a silver 
cleaner. Slight impressions on the stationary contacts will be 
caused by the pressure and wiping action of the movable contacts. 
Minor burrs or pitting can be allowed, and projecting 
burrs can be removed by dressing. Nothing more abrasive 
than crocus cloth should be used on the silvered contact surfaces.
Where serious overheating is indicated by the discoloration 
of metal and surrounding insulation, the contacts and 
spring assemblies should be replaced in line with the manufacturers’ 
instructions. 
Contact Pressure The circuit breaker should be closed manually to 
check for proper wipe, pressure, and contact alignment, 
and to ensure that all contacts make at approximately the 
same time. The spacing between stationary and movable 
contacts should be checked in the fully open position. Adjustments 
should be made in accordance with the manufacturers’ 
recommendations. 
Old contacts: Laminated copper or brush-style contacts found on 
older circuit breakers should be replaced when badly burned. 
Repairs are impractical because the laminations tend to weld 
together when burning occurs, and contact pressure and wipe 
are greatly reduced. They can be dressed with a file to remove 
burrs or to restore their original shape. They should be replaced 
when they are burned sufficiently to prevent adequate 
circuit-breaker operation or when half of the contact surface is 
burned away. Carbon contacts, used on older circuit breakers, 
require very little maintenance. However, inadequate contact 
pressure caused by erosion or repeated dressing might cause 
overheating or interfere with their function as arcing contacts. 
 The drawout contacts on the circuit breaker and the 
stationary contacts in the cubicle should be cleaned and inspected 
for overheating, proper alignment, and broken or weak 
springs. The contact surfaces should be lightly coated with a contact 
lubricant to facilitate ease of the mating operation. 
 Arc Interrupters. 
 General. Modern arc interrupters of medium voltage 
magnetic blow-out air circuit breakers are built with only inorganic 
materials exposed to the arc. Such materials line the 
throats of the interrupter and constitute the interrupter plates 
or fins, which act to cool and disperse the arc. The insulation 
parts of the interrupter remain in the circuit across contacts at 
all times. During the time that the contacts are open, these 
insulating parts are subject to full potential across the breaker. 
The ability to withstand this potential depends on the care 
given the insulation. 
 Particular care should be taken at all times to keep the 
interrupter assembly dry. The materials are not affected much 
by humidity, but the ceramic material especially will absorb 
water. 
The interrupters should be inspected each time the 
contacts are inspected. Any residue, dirt, or arc products 
should be removed with a cloth or by a light sanding. A wire 
brush or emery cloth should not be used for this purpose because 
of the possibility of embedding conducting particles in 
the ceramic material. 
Inspection checks An interrupter should be inspected for the following: 
(A) Broken or Cracked Ceramic Parts. Small pieces broken 
from the ceramics or small cracks are not important. Large 
breaks or expansive cracks, however, can interfere with top 
performance of the interrupter. Hence, if more than one or 
two broken or badly cracked plates are apparent, renewal of 
the ceramic stack is indicated. 
(B) Erosion of Ceramics. When an arc strikes a ceramic part 
in the interrupter, the surface of the ceramic will be melted 
slightly. When solidified again, the surface will have a glazed, 
whitish appearance. At low and medium currents, this effect is 
very slight. However, large-current arcs repeated many times 
can boil away appreciable amounts of the ceramic. When this 
happens, the ceramic stack assembly should be replaced. 
(C) Dirt in Interrupter. While in service, the arc chute assembly 
can become dirty. Dust or loose soot deposited on the inside 
surface of the arc chute can be removed by vacuuming or 
by wiping with cloths that are free of grease or metallic particles. 
Deposits can accumulate on ceramic arc shields from 
the arcing process. These deposits, from the metal vapors 
boiled out of the contacts and arc horns, can accumulate to a 
harmful amount in breakers that receive many operations at 
low-or medium-interrupting currents. Particular attention 
should be paid to any dirt on the plastic surfaces below the 
ceramic arc shield. These surfaces should be wiped clean, if 
possible, especially if the dirt contains carbon or metallic deposits. 
On breakers that operate thousands of times at low and 
medium currents, sufficient tightly adhering dirt can accumulate 
on the ceramic arc shields to impair proper interrupting 
performance. These arc chutes are of a very hard material, 
and a hard nonconducting abrasive is necessary for cleaning. 
A flexible, abrasive aluminum oxide disc on an electric drill 
can be useful in cleaning arc chutes. The ceramic arc shields 
might appear dirty and yet have sufficient dielectric strength. 
The following insulation test can be used as a guide in determining 
when this complete or major cleaning operation is 
required. The arc chutes of medium-voltage circuit breakers 
should withstand the 60-Hz-rated maximum voltage for one 
minute between the front and rear arc horns. In some applications, 
circuit breakers can be exposed to overvoltages, in 
which case such circuit breakers should have an appropriate 
overpotential test applied across the open contacts. Some 
manufacturers also recommend a surface dielectric test of the 
ceramic surfaces near the contacts to verify adequate dielectric 
strength of these surfaces. 
 Air-puffer devices used to blow the arc up into the 
interrupter should be checked for proper operation. One accepted 
method is as follows. With the interrupter mounted on 
the breaker in its normal position, a piece of tissue paper is 
placed over the discharge area of the interrupter and observed 
for movement when the breaker is opened. Any perceptible 
movement of the paper indicates that the puffer is functioning 
properly. 
Low-voltage air circuit-breaker arc chutes are of relatively 
simple construction, consisting primarily of a wedge-
shaped vertical stack of splitter plates enclosed in an insulating 
jacket. An arc chute is mounted on each pole unit directly above 
the main contacts. Arc interruptions produce erosion of the splitter 
plates. The lower inside surfaces of the insulating jackets will 
also experience some erosion and sooty discoloration. 
Observation: The arc chutes should be removed and examined as 
part of routine maintenance. If the splitter plates are seriously 
eroded, they should be replaced. If the interior surfaces of the 
enclosing jackets are discolored or contaminated with arc 
products, they should be sanded with sandpaper or replaced. 
Occasionally, the whole arc chute might need replacing, depending 
on the severity of the duty. 
Operating Mechanism. 
General. The purpose of the operating mechanism 
is to open and close the contacts. This usually is done by 
linkages connected, for most power breakers, to a power-
operating device such as a solenoid or closing spring for 
closing, and that contains one or more small solenoids or
other types of electromagnets for tripping. Tripping is accomplished 
mechanically, independently from the closing 
device, so that the breaker contacts will open even though 
the closing device still might be in the closed position. This 
combination is called a mechanically trip-free mechanism. 
After closing, the primary function of the operating mechanism 
is to open the breaker when it is desired, which is 
whenever the tripping coil is energized at above its rated 
minimum operating voltage. 
Check points The operating mechanism should be inspected for 
loose or broken parts, missing cotter pins or retaining keepers, 
missing nuts and bolts, and binding or excessive wear. All 
moving parts are subject to wear. Long-wearing and corrosion-
resistant materials are used by manufacturers, and some wear 
can be tolerated before improper operation occurs. 
 Excessive wear usually results in the loss of travel of 
the breaker contacts. It can affect operation of latches; they 
could stick or slip off and prematurely trip the breaker. Adjustments 
for wear are provided in certain parts. In others, replacement 
is necessary. 
The closing and tripping action should be quick 
and positive. Any binding, slow action, delay in operation, or 
failure to trip or latch must be corrected prior to returning to 
service. 
 The two essentials to apply in maintenance of the 
operating mechanism are KEEP IT SNUG and KEEP IT FRICTION 
FREE. 
 Breaker Auxiliary Devices. 
 The closing motor or solenoid, shunt trip, auxiliary 
switches, and bell alarm switch should be inspected for correct 
operation, insulation condition, and tightness of connections. 
 On-off indicators, spring-charge indicators, mechanical 
and electrical interlocks, key interlocks, and padlocking 
fixtures should be checked for proper operation, 
and should be lubricated where required. In particular, the 
positive interlock feature that prevents the insertion and 
withdrawal of the circuit breaker should be tested while it is 
in the closed position. 
 The protective relay circuits should be checked by 
closing the breaker in the test position and manually closing 
the contacts of each protective relay to trip the circuit breaker. 
. 
 Trip devices on low-voltage breakers should be tested periodically 
for proper calibration and operation with low-voltage/ 
high-current test devices. Calibration tests should be made to 
verify that the performance of the breaker is within the manufacturer’s 
published curves. It is very important that manufacturers’ 
calibration curves for each specific breaker rating be 
used. The fact that current-time curves are plotted as a band of 
values rather than a single line curve should be taken into 
account
 
 If the breakers are equipped with static-tripping devices, 
they should be checked for proper operation and timing in line 
with the manufacturer’s recommendations. Some manufacturers 
recommend replacement of electromagnetic devices with 
static devices in the interest of realizing more precision and a 
higher degree of reliability with the latter devices. 
 Molded case circuit breaker
 A molded-case circuit breaker consists of two basic 
parts. One part consists of the current-carrying conductors, 
contacts, and appropriate operating mechanism necessary to 
perform the circuit-switching functions. The second part consists 
of the protective element, including the tripping mechanism 
associated therewith. 
. 
Application Considerations. Molded-case circuit breakers 
will trip from exposure to continuous currents beyond 
their ratings, and many trip from unduly high ambient temperatures, 
from poor or improper connections, from damaged 
plug-in members, and from other conditions that transfer 
undue heat to the breaker mechanism. Some of these 
conditions violate application specifications. A molded-case 
circuit breaker applied in a panelboard should not be loaded 
in excess of 80 percent of its continuous current rating, where 
in normal operation the load will continue for three hours or 
more. 
Phase-Fault Current Conditions. A typical molded-case 
circuit breaker is equipped with both time-delay and instantaneous 
tripping devices. Time-delay tripping has inverse time 
characteristics that provide a shorter tripping time for higher 
overloads. Under moderate, short-duration overloads, the circuit 
breaker allows sufficient time for applications such as motor 
starting. Under severe overloads, the circuit breaker will 
trip quickly, providing adequate protection for conductors 
and insulation. For high-fault currents, the magnetic tripping 
device responds to open the circuit breaker immediately.
 
 Ground-Fault Tripping. It should be recognized that 
standard molded-case circuit breakers are not generally 
equipped with ground-fault sensing and protection devices 
and, therefore, will not normally trip and clear low-level 
ground faults that can do immense damage. 
 Types of Molded-Case Circuit Breakers. 
 Molded-case circuit breakers can generally be divided 
into three major categories depending on the type of trip unit 
employed: 
(1) Factory sealed, noninterchangeable trip 
(2) Interchangeable trip 
(3) Solid state 
.
Types of Maintenance. Maintenance of molded-case circuit 
breakers can generally be divided into two categories: mechanical 
and electrical. Mechanical maintenance consists of inspection 
involving good housekeeping, maintenance of proper 
mechanical mounting and electrical connections, and manual 
operation as outlined in the following paragraphs. 
 Inspection and Cleaning. Molded-case circuit breakers 
should be kept clean of external contamination so that internal 
heat can be dissipated normally. Further, a clean case will 
reduce potential arcing conditions between live conductors, 
and between live conductors and ground. The structural 
strength of the case is important in withstanding the stresses 
imposed during fault-current interruptions. Therefore, an inspection 
should be made for cracks in the case, and replacements 
should be made if necessary. 
 Loose Connections. Excessive heat in a circuit breaker 
can cause a malfunction in the form of nuisance tripping and 
possibly an eventual failure. Loose connections are the most 
common cause of excessive heat. Periodic maintenance 
checks should involve checking for loose connections or evidence 
of overheating. Loose connections should be tightened 
as required, using manufacturers’ recommended torque values. 
Molded-case circuit breakers having noninterchangeable 
trip units are properly adjusted, tightened, and sealed at the 
factory. Those having interchangeable trip units installed away 
from the factory could overheat if not tightened properly during 
installation. All connections should be maintained in accordance 
with manufacturers’ recommendations. 
 Mechanical Mechanism Exercise. Devices with moving 
parts require periodic checkups. A molded-case circuit 
breaker is no exception. It is not unusual for a molded-case 
circuit breaker to be in service for extended periods and never 
be called on to perform its overload-or short-circuit-tripping 
functions. Manual operation of the circuit breaker will help 
keep the contacts clean, but does not exercise the tripping 
mechanism. Although manual operations will exercise the 
breaker mechanism, none of the mechanical linkages in the 
tripping mechanisms will be moved with this exercise. Some 
circuit breakers have push-to-trip buttons that should be 
manually operated in order to exercise the tripping mechanism 
linkages.
Friday, February 13, 2009
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment